Vertex Drive System Log

as of Saturday, 09-Apr-2016 20:37:40 AST

Go to Most Recent Entry

NameEmailDateComment
Luis Murraylmurray@naic.eduWednesday, February 2, 2005 10:36:08January 6 2005, Overtemperature failure at Vertex's Shack. Both air conditioner units were off because 480VAC breaker was tripped. Bill Genter said that temperature at the Vertex's Shack was over 100 degrees Farenheit.
Luis Murraylmurray@naic.eduWednesday, February 2, 2005 11:50:04January 20 2005, Overtemperature failure at the Vertex's Shack again. The same 480VAC breaker tripped and both air conditioners were down. After the Vertex's Shack was cooled, Azimuth wasn't moving in one direction using the "traking mode". Problem was found at the PLC. Overtemperature damaged the Siemens CPU 928B PLC (Vertex's Drive's System Control Computer). Azimuth axis
Luis Murraylmurray@naic.eduWednesday, February 2, 2005 11:55:44January 22 2005, We helped Maintenance Department to check the 480VAC 20Amp breaker today. Breaker looked OK but one of the air conditioner units was drawing more than 30 Amps when starting. Starting capacitor was replaced for that AC and the breaker was replaced with a 40 Amp.
Luis Murraylmurray@naic.eduWednesday, February 2, 2005 14:05:18January 29 2005, Gregorian Dome pre-limits and final limits were at a different setting. Lower limit was around 3 degrees. After evaluation we found that the problem was at the "cam switch". It is located at the opposite side of the GD encoder and it contains the pre and final limits for both up and down limits. Our recomendation is to replace the "cam switch" with individual switches.
Luis Murraylmurray@naic.eduWednesday, February 9, 2005 16:09:36Feb 4 2005, Discrete limit switches were installed at the Gregorian Dome. These switches are replacing the "Cam Switch" wich included the pre-limits and final limits. Emergency limits were tested and are OK. Final limits are located .04 degrees after the Emergency limits and pre-limits are .04 degrees after the final limit.
OCocolon@naic.eduFriday, January 22, 2010 11:29:00Log Test
WI, OCwiguina@naic.eduTuesday, April 6, 2010 14:24:07Se le dio reset al Vertex Drive Sysem.
OC, WIocolon@naic.eduThursday, August 26, 2010 09:57:13Se enviaron 2 motores a reconstruir el martes 24 Model# B-604-A-B2-B9S-095 SN 95J604A-325 Model# B-606-A-B2-B95-095 SN 95J606A-244
OC, WIocolon@naic.eduThursday, August 26, 2010 10:03:45Se reemplazo en 08/12/2010 el motor M51 SN 95j604A-325 para mantenimiento por SN 95J604A-324
Ocolon, W.Iguinaocolon@naic.eduFriday, December 6, 2013 09:14:34En el relay PD-28CR02 se movö­o los contactos 13 y 14 a 43 y 44. devido a una caida de voltage que evitava encender el Vertex despues de un power dip.
Ocolon, WIguinaocolon@naic.eduFriday, December 6, 2013 09:25:16Se Reemplazo el AMP 32 el 11/26/13. motro se quedaba sin torque
ocolon, wiguinaocolon@naic.eduWednesday, December 11, 2013 10:16:40se reemplazo sw de las ruedas del domo.
Ocolon, WIguinaocolon@naic.eduWednesday, December 18, 2013 09:27:54se reempazo el brazo de un switch de las ruedas del domo
WIP/OCwiguina@naic.eduMonday, June 16, 2014 13:08:19Remplasö© el Amp 51 Ser.95j-7583 del AZ 06/12/14 y lo enviamos a reparar el 06/13/14.
WIPwiguina@naic.eduTuesday, July 15, 2014 14:54:2007/14/14 llego reparado un amplificador BDS4A-220H/604A2 que estaba en la posiciö¨n 51 del vertex.
WIPwiguina@naic.eduTuesday, July 15, 2014 14:58:5307/14/14 Llegaron los abanicos nuevos de los amplificadores del Vertex
WIPwiguina@naic.eduTuesday, July 29, 2014 07:43:297/26/2014 Reemplacö© un amplificador de la caseta uno MD. BDS4A-220H/606A2 SN.95J-7571.
JRwilly.59@live.comTuesday, July 29, 2014 07:50:397/28/2014 Jorge Rodriguez Reemplazö¨ el amplificador #22 del Azimuto MD.BDS4A-220H/606A2 SN.99J-1709...
WIP/OCwiguina@naic.eduTuesday, July 29, 2014 13:40:1107/29/14 Reemplazamos el amp. 52 del AZ BDS4A-220H/604A2 para cambiarle el abanico.
WIPwiguina@naic.eduTuesday, July 29, 2014 13:50:3707/29/14 Encontramos el cable del motor 22 del GD partido dentro del el cable drom y lo reparamos... El amp.22 MD BDS4A-220H/606A2 SN 99J1709 Estö¡ bueno le vamos a cambiar el abanico para volverlo a usar...
WIP/JRwiguina@naic.eduThursday, August 14, 2014 20:00:08Reparamos el cable de un interruptor de emergencia del AZ... Estaba corroö­do y partido haciendo corto circuito.
WIPwiguina@naic.eduFriday, August 15, 2014 10:24:48Hoy a las 12:45AM El breaker de AC del aire acondicionado del Vertex estaba OFF la temperatura del gabinete estaba alta segun el operador me indico, lo puse en ON y el aire acondicionado el selector de temperatura del Aire estaba en 50 grados demasiado bajo lo puse en 68 grados y continuo trabajando.
WIPwiguina@naic.eduMonday, August 25, 2014 09:58:01Magna enviö¨ el Amplificador BDS4A-220H/604A2 (S.N. 95J-7571) reparado listo para usar.
WIP/OC/JRwiguina@naic.eduFriday, January 16, 2015 08:58:12Cambiamos el amplificador que estaba en la posiciö¨n 11 del AZ por falla de overcurrent y el abanico del amplificador en la posiciö¨n 12.
WIP/OCwiguina@naic.eduFriday, April 10, 2015 08:57:35Remplazamos los abanicos de los amplificadores del Vertex todos estö¡n funcionando, y y mande a pedir 16 abanicos para tenerlos de repuesto, Cambiamos la configuraciö¨n de los abanicos de las puertas del vertex para que el aire friö¨ fluyera a en la misma direcciö¨n de delos abanicos de los amplificadores.
OCwiguina@naic.eduThursday, July 2, 2015 13:23:24Osvaldo vino de emergencia a cambiar el encoder de 1 del AZ, Yo lo enviö© a repara y Wanda pido una cotizaciö¨n para comprar uno o dos nuevos.
WIP/OCwiguina@naic.eduWednesday, August 12, 2015 12:00:25Encontramos unos cables deteriorados y corroö­dos por la exposiciö¨n al ambiente en el sistema del Vertex, AZ, GD, CH que podrö­an en un futuro cercano causar problemas, identificamos remplazo y como hacer para que no vuelva a pasar, vamos a remplazar los micro switch de los emergency stop en toda la platafoma , coordinamos para comenzar a remplazar el dö­a 20 de agosto 2015...
WIP/OCwiguina@naic.eduFriday, September 4, 2015 08:47:34Instalamos tuberö­a y cables en el ö¡rea del AZ para comenzar a remplazar los cables deteriorados del sistema de control del Vertex...
WIP/OCwiguina@naic.eduFriday, September 4, 2015 10:51:19Remplazamos el power supply de 24v de la antena 12 metros.
WIP/OCwiguina@naic.eduFriday, September 18, 2015 15:31:37Remplazamos el relay del Cable Car en el Vertex.
WIPwiguina@naic.eduMonday, September 28, 2015 08:50:31Remplace el amplificador 4.1 de el GD por falla de overtemp, tu ve q remplazar el q de nuevo el mismo por falla de over current, los dos amp. defectuosos se enviaron a Magna para reparaciö¨n.
WIPwiguina@naic.eduMonday, September 28, 2015 08:51:28Remplazamos un motor del GD con problemas con el freno.
WIP/OCwiguina@naic.eduTuesday, September 29, 2015 11:03:50Remplazamos y re ubicamos los abanicos de los power supply de la caseta 1 y del segundo grupo de motores de el domo para mejor acceso a los mismos en caso de volverlos a remplazar, tambiö©n remplazamos un abanico defectuoso del amplificador en la posiciö¨n 3.2 del domo.
WIP/OCwiguina@naic.eduMonday, October 19, 2015 11:22:16Enviamos dos motores listos para instalar uno de DG/CH1 y otro de AZ por si falla alguno sea mas rö¡pido el cambiar...
WIP/OCwiguina@naic.eduTuesday, January 12, 2016 15:13:08We replace the encoder 1 and calibrate the AZ for position 270áº. AZ1, AZ2 corrected 6,000,000/counts 18726992.